A transformer turns ratio meter measures the ratio of a transformer’s primary and secondary windings. It can also measure other parameters, such as voltage ratio, phase displacement, and excitation current.
It is suitable for operation in energized switchyard condition. It is portable and light in weight. It also measure turns ratio of transformers having different vector groups.
| ||
Sr. No. | Specs | |
1 | Turns Ratio Measurement Range and Accuracy | Turns Ratio Range 8 to 10 V AC 35 to 40 V AC 80 to100V AC 0.8 to 1000 0.1% 0.1% 0.1% 1000 to 2000 0.15% 0.1% 0.1% |
2 | Excitation current Range and Accuracy | 0 to 1000 mA with resolution of 0.1mA, 4½ digit Resolution with less than1% Accuracy |
3 | Phase Deviation Range and Accuracy | +/-90 degrees (one decimal point for minute display and two decimal point for degree display |
4 | Test Voltage | User selectable : 240V AC, 100, 40 and 10V @ 1A |
5 | Power | 240V ± 20%, AC 50 Hz. |
6 | Display | Touch screen colored display viewable in direct sunlight |
7 | Computer Interface | USB |
8 | Key Board | Touch Screen |
9 | Printer | External Printer – Optional |
10 | Operating Temperature | Operating: -10° .. 50°C |
11 | Storage Temperature | Storage: -20° … 70°C |
12 | Indication | Safety indication |
Copyright 2024 Rectifiers & Electronics Pvt. Ltd. All Rights Reserved.