AC High Voltage Low Capacity Test Sets are essential tools for ensuring the quality and safety of electrical equipment. They specialize in testing a wide range of components, including insulators, transformers, and current transformers, all in compliance with National and International standards.
Each tester undergoes rigorous manufacturing processes with multi-stage testing to guarantee consistent performance. These testers come in various configurations, with air, oil, or a combination of air and oil cooling depending on the model. Offering a variety of testing capabilities, it includes dry withstand, wet withstand, breakdown voltage, and pollution tests, with voltage ratings up to 800kV and current capacities up to 200kVA.
Standard Accessories
Optional Accessories
Parameters | Description | |
1 | I/p Voltage | 220/230V or 380/400V, 50 or 60HZ AC supply |
2 | O/p Voltage | Up 800KV and 250mA |
3 | Capacity | Up to 200KVA |
4 | Timer | 0-9999 Sec./min. Digital |
5 | Control | Type 1 – Manual or motorized voltage adjustment with push-button HT activation. Type 2 – Digital panel with optional computer connectivity. Type 3 – Fully automated: PLC-based system with integrated computer, HMI, and printing capabilities. |
6 | Metering | Voltmeter: One Digital type connected on the HT side to indicate the output voltage Scale: 0-800 kV AC. Ammeter: One Digital type ammeter Connected on the earth side to indicate the leakage Current on the sample under test. Scale: 0-500mA Applicable only for type -1 For type -2 and type 3 metering is self-contained |
7 | Protection | Tripping – A fast-acting DC relay cuts power when the current surpasses the set limit. Overload – This is used as a secondary protection in case the input loads exceed the preset value. Overvoltage – This is used as a secondary protection in case the output voltage exceeds the preset value. |
8 | Interlocking | Zero Start Interlock – The unit will have zero start interlocking to avoid the transients on the HV transformer. Provision for cage door interlocking shall also be provided. Earth interlock- It ensures that HV will not actuate until good earthing is provided. |
9 | Termination | The HT output on suitable HT insulators and other points at earth potential will be brought out on suitable insulator |
10 | Control Panel | The control panel is designed for five unique purposes. 1 – Control 2 – Measure 3 – Protect (Active and Passive) 4 – Tripping 5 -Annunciate |
11 | HV Transformer | We craft our transformers to IS/IEC standards, offering single and multi-stage step-up options for versatile voltage requirements. Built with premium materials sourced globally, our units boast vacuum-impregnated coils insulated with top-tier EHV grade oil, meeting or exceeding industry benchmarks. |