Sr. No. |
Parameters |
Description |
Remarks |
1 |
Maximum Capacity |
Up to testing of 30MVA for Losses Measurement and Upto 220MVA for other Tests, 11kV,22kV,33kV,66kV,132kV and 220kV Capacity of Transformers |
|
2 |
Input Supply Voltage |
220/230V, 50/60HZ or 380/400V, 50/60HZ Supply |
|
3 |
Frequency |
50HZ/60HZ |
|
4 |
Booster Transformer |
Our maximum capacity of manufacturing Booster Transformer is up to 2MVA |
For Transformer Test Bench Capacity of Booster Transformer designed as per the capacity of transformer to be tested. For Example For testing of 5 MVA Transformer the capacity of Booster Transformer will be 300kVA and so on. |
5 |
Auto Transformer |
Our maximum capacity of manufacturing Auto Transformer is up to 2000A |
For Transformer Test Bench Capacity of Auto Transformer designed as per the capacity of transformer to be tested. For Example for testing up to 5MVA Tranaformer the capacity of Autotransformer will be 400A and so on. |
6 |
Capacitor Bank |
Our maximum capacity of manufacturing Capacitor Bank is up to 2000kVAr |
For Transformer Test Bench Capacity of Capacitor Bank designed as per the capacity of transformer to be tested. For example for testing up to 5MVA transformer the capacity of Capacitor Bank will be 400kVAr and so on. |
7 |
High Voltage Tester |
Our maximum capacity of manufacturing AC High Voltage Test Set is up to 800kV and 3000kVA. |
For Transformer Test Bench Capacity of High Voltage designed as per the capacity of transformer to be tested. For example for testing up to 11kV of Transformers the capacity of AC High Voltage Set will be 30KV and so on. |
8 |
DVDF Test |
Our maximum capacity of manufacturing DVDF test set is up to 10MVA |
For Transformer Test Bench Capacity of DVDF designed as per the capacity of transformer to be tested. For example for testing of 5MVA transformer the capacity of DVDF will be 50kVA and so on. |
9 |
Integrated Control Panel |
Having single control for all the test like No Load/ Full Load, HV Test , DVDF test etc. |
|
7 |
Control |
Type 1- The unit can be manual/motorized control for voltage variation and push button controlled for each test. Type 2- The unit can be complete with on board digitized panel with or without computer connectivity. Type 3- The unit can be PLC based complete with computer, HMI memory, printer etc. for operation. |
|
8 |
Protection |
Overvoltage , Overcurrent, Earth Fault and Zero start interlock |
|
9 |
Interlocks |
Earth Interlockand and Zero start interlock |
|
10 |
CT and PT |
CT and PT used of 0.1/0.2/0.5 Class accuracy - as per Requirement |
Capacity of CT/PT's designed as per the capacity of transformer to be tested. |
10 |
Transformer |
The transformer used in HV test, Variac and booster transformer are designed and manufactured as per IS /IEC guidelines. Single / Multiple stage stepup transformers are utilized for achiving the desired voltage. The units are designed and manufactured using the preeminent material from India and Abroad. |
|
11 |
Generators and Motors of DVDF |
Generator used in DVDF are either of three types Brushless Generator DC Excitation Slip ring type Motor is of induction type |
|